Due to its function modules, the UVR1611 unit can be freely programmed to suit any system configuration for heating space management. As each function module can be implemented many times over, it is also possible to realise complex control systems, such as solar thermal systems with several collector panels and tanks, or several weather-controlled heating circuits. It has the following properties: -
16 sensor inputs for KTY10 or PT1000 sensors (two of which also as pulse inputs and one as a 4-20mA or 0-10V analogue input) -
4 speed-controllable outputs and 7 relay outputs -
Option to fit two additional outputs with a relay module -
Operation via scrolling wheel and large display -
Integrated potentiostat for the electrical tank corrosion protection -
CAN bus for data exchange with other devices, or additional UVR1611 units -
Infrared interface for software updates Art. no.: 01/UVR1611K (with bracket clamp for wall mounting) | Accuracy: | typ. ±2% | | Operating voltage: | 230 V AC 50-60 Hz | | Power consumption: | max. 4 VA | | Rated current load: | max. 1.5 A per output, or 5 A in total | | Fuse: | 6.3 A quick-blow (unit + outputs) | | Transformer: | short-circuit proof | | Protection class: | II - protective insulation | | Protection degree: | IP40 | | Dimensions: |
| | Weight: | g | | Permissible ambient temperature | 0 to 45 °C | Model: UVR1611-K with bracket clamp for wall mounting UVR1611-S with ready-to-plug rear panel for installation in a control panel Sensor packages: Basic package GP1: 1 PT1000 collector sensor, 1 KTY boiler sensor, 6 KTY storage tank sensors, 6 140 mm immersion sleeves , 1 power cable Basic package GP2: 1 PT1000 collector sensor, 1 KTY boiler sensor, 5 KTY storage tank sensors, 1 outdoor sensor, 1 room sensor, 5 140 mm immersion sleeves, 1 power cable Expansion package EP1: 1 outdoor sensor, 1 room sensor, 4 KTY storage tank sensors, 3 140 mm immersion sleeves Expansion package EP2: 5 KTY storage tank sensors, 1 1.5 m³ flow sensor, 2 140 mm immersion sleeves, 2 40 mm immersion sleeves | Manuals: |
| | |
| | |
| | |
| | |
| | |
| | |
| | | | Firmware:
| Here you will find the current version of the operating system
| | | | Software:
| TAPPS, the programming software for UVR1611 | This controller is equipped with individual function modules which can be freely interconnected. A detailed description of all function modules would require more space than is available here. Please see the Manual for more information | Overview of function modules | | | Solar control Solar priority Start function Cooling function Heating circuit controller Mixer control Comparison Loading pump Heating requirement Hot water requirement Boiler cascade Circulation | PID control (speed control) Analogue function Profile function Logic function Time switch Timer Synchronisation Heat meter Meter Maintenance Function control | | |