| Version 2.12 |
22.07.2011 |
Modifications:
- The IP address will be adopted by F-Editor and also written back to BL-NET correctly.
- Analog and digital CAN inputs (network output) on BL-NET will be initialized with 1 and not with 0.
- Timeout during CAN data logging is adjusted to the save criterion. Therefore the problem is solved, that sometimes files with 1 minute save criterion (or multiple) are not stored.
- Now Cookies contain only numbers or letters, up to now problems with special characters existed.
- Because of safety reasons HTTP GET inquiries will be started with “bl” and only then the datas will be sent.
- HTTP GET inquiries will be checked extra for validity.
- The command 82h corresponding to TA protocol will be supported.
|
Version 2.11
|
06.07.2011 |
Modifications:
- All http GET requests will be sent with an prefix “bl”. This is a further security of possible unknown requests.
- Bug-fix actualization of time stamp in CAN data logging ( if that problem occurred logging was stopped).
- Bug-fix on creation of cookies in case of special characters
|
|
Version 2.10
|
17.06.2011
|
Modifications:
- Bug-fix on changing of bit areas (e.g., on selection of days in time windows), occurred only in version 2.09
- Bug-fix on text display (only version 2.09). Some texts have been display incorrectly resp. incompletely in some languages.
- Bug-fix on texts (Italian and Czech)
- Additional security query in CAN data logging for reading correct frame data
- Bug-fix on display of performance (kW) and heat quantity (kWh) via network input variables
- Bug-fix: Can data logging read after two times non-receive of data the next frame. That caused exchanged data in Winsol. Now Winsol waits for new data until receive.
- Bug-fix: Negative temperatures on network inputs will be displayed right.
- Addition of rest for valid logging pointer; for this reason it cannot be perverted.
|
|
Version 2.09
|
03.05.2011
|
Modifications:
- Bug-fix: Temperature of RAS read in via CAN network input will be displayed correctly now on the BL-NET
- Addition of humidity (unit) in CAN data logging
- Bug-fix: Display of negative temperatures in browser operating
- Memory will be deleted when changing the CAN data logging configuration
- Operating system update of BL-NET is only possible during supply via CAN bus
|
|
Version 2.08
|
31.03.2011
|
Modifications:
- Bug-fix: Digital data for CAN frame 2 of Online diagram have been displayed wrong (3 values above)
- Bug-fix on calculation of check sum on IP header
- Improvement of data recovery for TA protocol data via Ethernet
- In case of HTTP abandonment the Online diagram routines will also be reset.
- Addition of repeat function for Ethernet for the last two packets.
- Addition of overflow request for RAS PT
|
|
Version 2.07
|
28.03.2011
|
Modifications:
- Bug-fix on CAN data logging switching-over winter to normal time
- Bug-fix on quick actualizing of pages in browser (above all of values of Online diagram)
|
|
Version 2.06
|
21.03.1011
|
Modifications:
- Bug-fix on display of leading „0“ of speed stage in Online diagram.
- Units in CAN data logging, which cannot been displayed in Winsol, will be displayed with right numeric value but with wrong unit, as the units are deposited unchangeable in Winsol.
- Switching over between Can data logging and data logging via DL bus all data will be deleted, which already have been logged.
- Bug-fix on modification of scaling values on voltages in inputs.
- Bug-fix on loading of second page of Function overview (In case of back to last page problems occurred on loading this page, if values have been changed on page 1 before.).
- Bug-fix on transmitting duration of digital outputs of BL-NET via SMS.
|
|
Version 2.05
|
10.03.1011
|
Modifications:
- Bug-fix on upload of gif-file; problems on special strings at begin of 64 byte packet (21h 43h)
- Following dimensions will be output as temperatures on CAN Data logging: l/pulse, V, mA, Pulse, kOhm, km/h, bar
- Bug-fix on modification of values at the controller via browser (Values have been modified to 12 automatically on changing.).
- Bug-fix on loading gif-file.
- Evaluation of Cookies revised, problems with mobiles solved.
|
|
Version 2.04
|
23.02.2011
|
NEW:
- If CAN data logging in Online diagram is selected, but Can data logging is not active, “error” will be displayed in Online diagram.
- If passwords are selected and password “nur ansehen” (read only) is set to “12345”, the Online diagram can be viewed without password.
Modifications:
- Bug-fix loading of HTML files with size many times over 64
- Bug-fix loading of HTML files with size many times over 64+1
- Bug-fix in display of performance (kW) for heat quantity counter 2 in Online diagram (wrong addressed)
- Bug-fix: Using Internet Explorer sources have partly not been displayed for selection
- Window sizes enlarged for translated pages from CAN bus, so that buttons can be displayed in same line.
- Restriction of User rights to Online diagram, Function overview and GSM settings.
|
|
Version 2.03
|
09.02.2011
|
NEW:
- Menu „Daten“ („Data“) is renamed to „Datenverwaltung“ („Data administration“).
- Text in menu “Datenlogging” (“Data logging”) is changed to “Meldung an GSM Kontakt bei 0% Speicherauslastung“ („Message to GSM Contact at 0% memory capacity”).
Modifications:
- Bug-fix: Readout of actual CAN data logging data via USB.
- Bug-fix in display Function overview, if no data are available in Function overview.
- Addition of Retransmit-routine in TCP in case of lost data packets.
|
|
Version 2.02
|
07.02.21011
|
NEW:
- Firmware for BL-NET is written completely new.
- Now it is possible to send e-mails via GSM Module too
|
|
Version 1.43
|
23.07.2010
|
Modifications:
- Bug-fix in update of operation system for CAN I/O Module (So far it was not possible!).
|
|
Version 1.42
|
|
Modifications:
|
|
Version 1.41
|
1.3.2010
|
NEW:
- Update of operating system is possible for CAN I/O Module 35 too.
Modifications:
- Graphics for Online diagram in new format (from TAPPS 1.26) will be justified left to frame (display area). Graphics have been centered in frame in version 1.40. I.e., if frame in TAPPS had not exactly the same size as graphics, the positions of graphics and measuring values did not correspond in Online diagram.
- Telephone number filter for GSM queries improved; received number must start with +.
- Bug-fix: In GSM settings values have sometimes been displayed in undefined analog inputs.
|
|
Version 1.40
|
|
Modifications:
- Bug-fix in Online diagram: values for kWh between 384.0 and 409.5 have been displayed as 999.9.
- Bug-fix: Standby and time have been transmitted wrong in case of SMS for External switch of function Heating circuit control.
- Bug-fix: OFL and UFL for CAN data logging have been displayed wrong
- New implementation of Online diagram (only values will be reloaded).
- Pressure will be transmitted as temperature in CAN data logging; up to now no values.
- Bug-fix: No answer has been transmitted in case of digital command “ON” via SMS.
|
|
Version 1.39 BETA
|
|
NEW:
- CAN Data logging for 8 frames
- Operating system update for CAN Bus converter inserted.
Modifications:
- Display of digital statuses in Online diagram changed from ON, OFF to „EIN“ „AUS“.
- Bug-fix display of kWh in Online diagram in combination with UVR61-3.
- Bug-fix data logging of UVR61-3; only 1 data record has been stored.
- Bug-fix in transmission of heating circuit statuses via SMS to controller.
|
|
Version 1.37
|
06.03.09
|
Modifications:
- Bug-fix: When BL-NET was made powerless after data logging, wrong initializing during data readout occurred and it was not able to readout logged data.
- Bug-fix: Function data were not transferred in case of download.
- Bug-fix: At GSM options (SMS after reset, phone number, filter,...) String “ON” has been displayed with a third random character in some browsers.
- Bug-fix in Delete SMS Definitions: Digital definitions have not been deleted.
- Bug-fix: An event in digital network inputs could be defined, but it was displayed wrong.
- “SMS bei X% belegtem Speicherauslastung senden!” (Send (SMS) text message at X% assigned memory capacity!) released for DL (data link) now.
- Bug-fix in data logging after overflow of memory (stored every 10 seconds).
- Bug-fix: Data got lost after switch-over of interfaces for reading out data.
- Comma in values of heat quantity counter in case of loading via network added.
|
|
Version 1.36 BETA
|
18.02.09
|
NEW:
- Extension data link for evaluation of ESR21
Modifications:
- Bug-fix in ON/OFF functions of additional options (number filter, SMS in case of reset and SMS in case of nodes blackout) for GSM Module.
- Bug-fix in addressing of network variables for Online diagram.
- Bug-fix string Bootloader
- Bug-fix: BL-NET displayed wrong nodes in menu network in case of more than 8 nodes at CAN bus.
- Change from “Ein/Aus” to “ON/OFF” in SMS options.
- Bug-fix in display of 2 heat quantities in Online diagram
- Data link at UVR61-3 from version 5.0 and UVR1611 from version A3.00 adjusted.
- Watchdog function revised for improvement of reliability.
|
|
Version 1.35
|
26.09.08
|
Modifications:
- Bug-fix: In Online diagram interruptions of sensor inputs have been displayed on controller with 402.5; now corrected, so that 999 are displayed.
- Bug-fix: Because of an initializing error DC was returned in case of Test-IP (Test-COM).
|
|
Version 1.34
|
22.09.08
|
Modifications:
- Bug-fix in data logging. Now time stamp will only be transferred if data are really valid.
|
|
Version 1.33
|
13.08.08
|
Modifications
The browser menu structure has been changed, so that the network inputs and outputs are signed as suchlike. Up to now they were only found in GSM settings.
Temporal procedure in program of BL-NET has been optimized. Therefore synchronization errors occurred frequently in earlier versions. Malfunctions of data link (DL) have often been read in as valid data records in earlier versions; this has been corrected.
Temperatures in Online diagrams, which are read in from network, have been displayed with “grd C”; this was corrected to “°C”.
Up to now changes of operation mode sent by SMS had always priority. In future the message will be sent on CAN bus only three times in intervals of 5 minutes so that operation mode can be changed again directly on controller.
Bug-fix in update operating system of CAN Monitor with version <1.16.
|
|
Version 1.30
|
24.04.08
|
- Bug-fix in identification of devices on data link (DL); malfunctions on data link have been identified as new device and therefore the former data have been deleted.
|
|
Version 1.29 BETA
|
22.04.08
|
- Bug-fix Online diagram: Long graphics load times and partly deformed graphics occurred if network inputs have been called up.
Actual performance of heat quantity counter 2 was displayed wrong.
- Bug-fix: Recording gaps in data logging
|
|
Version 1.28
|
17.03.08
|
NEW
- CAN network inputs of BL-NET (setting can be made in GSM settings) can be displayed in Online diagram.
- Dimensions of network inputs of BL-NET will be loaded automatically from concerning devices after restart of BL-NET; setting of scaling is no more necessary.
- Free setting of HTTP Port (factory setting = Port 80).
- From version 1.28 function data of following devices can be maintained on BL-NET:
UVR1611, CAN Monitor (from version E2.01), CAN I/O Module (from version 2.00) and CAN bus converter.
- Function data of BL-NET itself can be saved and restored on PC too.
- Online diagram can be loaded via software Memory Manager (from version 2.07) (*.gif and *.html).
Modifications:
- Bug-fix: If UVR1611 on terminal DL2 and device without internal time on terminal DL2, time of DL1 was used anyway.
- Because of few problems with GSM Module and providers, new registration of GSM Module occurs to GSM net every 12 hours.
- Online diagram can be looked at from everybody without password.
- Remove of SMS as e-mail, as it is not supported of most of providers.
- If heat quantity counters are deactivated, display of concerned values is “- -“.
- Bug-fix in user access via BL-NET: User was not able to change time programs in function Synchronization.
Incompatibilities:
- It is necessary to install Memory Manager with version 2.07 or higher before updating BL-NET from version <1.28 to version 1.28!
- All function data get lost when updating from elder versions as 1.28 to version 1.28 or higher!
- Versions <1.28 are not allowed to load to BL-NET after update BL-NET to a version ≥ 1,28!!!!!
- For this version a new Dataflash must be built in into BL_NET with serial number ≤ 1307!!!
|
|
Version 1.26 Boots. B1.02
|
11.01.08
|
Modifications:
- Bug-fix data logging (After plug out of all power supplies all data got lost, only version 1.25.)
|
|
Version 1.25 Boots. B1.02
|
19.11.07
|
Modifications:
- Bug-fix saving destination of SMS (NOTE! Destinations have been relocated!)
- Selection "nur ansehen ohne Passwort" (read only without password) will be saved in Dataflash now.
- Communication with GSM Module will be checked for errors.
- Bug-fix data logging (A wrong diff was calculated in case of difference criterion crossover from zero to minus or minus to zero.)
|
|
Version 1.23BETA Boots. B1.02
|
17.09.07
|
Modifications:
- Password lock will be activated after 3 unsuccessful attempts (deactivation by two times input of right password).
- GSM Module will be observed by Watchdog.
- Internal device code will be skipped in case of elder controller operating systems (otherwise problems in data transfer)
- Timeout for Cookies reduced to 3 minutes
|
|
Version 1.22 Boots. B1.02
|
03.07.07
|
Modifications:
- Bug-fix in Analog function (output could not be modified)
- Time and date can be applied by commands to Online diagram.
- Node 63 available in menu “Datenverwaltung” (data administration); this node can be selected now if operating system update is interrupted.
- Now radiation values are displayed in Online diagram correctly.
|
|
Vers.1.21BETA B1.02
|
22.05.07
|
Modifications:
- Password protection has been revised.
|
|
Vers.1.20 B1.02
|
20.03.07
|
Modifications:
- Evaluation of SMS revised.
- Addition of Online diagram
- Password query revised
- Bug-fix in PID parameter setting
|
|
Vers.1.19B1.02
|
23.02.07
|
Modifications:
|
|
Vers.1.18 B1.02
|
13.02.07
|
Modifications:
- Bug-fix data transfer (BL-NET lost data)
- Revision of data logging with UVR61-3
- Addition “Datenverwaltung” (data administration) via browser
|
|
Vers.1.17 B1.02
|
26.01.07
|
Modifications:
- Preparation password protection
- Speed of Ethernet connection improved
- Revision of GSM Module functions
|
|
Vers.1.16beta B1.02
|
23.12.06
|
Modifications:
- Password protection inserted
|
|
Vers.1.15 B1.02
|
12.12.06
|
Modifications:
- Actualization of TCP/IP Stack to version 3.75
- Extension of GSM functions with “SMS as e-mail”.
- Possibility of switch-over operation mode of heating circuit via SMS (Time, Normal, Lowered, Standby or Intern)
- Revision of data link DL
- Bug-fix in battery operation mode
|
|
Vers.1.14ß B1.01
|
09.11.06
|
Modifications:
- Revision of GSM functions
- Display of UVR1611 pages improved
- Settings of data link adjustments for battery operation mode improved
|
|
Vers. 1.13 B1.01
|
17.10.06
|
Modifications:
- Bug-fix in USB communication
- Bug-fix in data transfer controller version <2.00
- Bug-fix in data logging
- Possibility to log network inputs of UVR1611 via data link DL
- Communication with Winsol (from version 1.16) and Memory Manager (from version 2.05) via Ethernet possible too.
|
|
Vers. 1.11 B1.01
|
20.08.06
|
Modifications:
- Update program for Bootloader inserted.
- Versions < 1.11 not possible from here!
|
|
Vers. 1.10 B1.00
|
|
Modifications:
|
|
Vers. 1.02 B1.00
|
|
Beta test version with data link DL
|
|
Vers. 1.01 B1.00
|
|
First version
Data logging not yet possible
|