Readme UVR1611

Information about modifications Version 3.xx

A3.25
B3.23

11.2.2011

MODIFICATIONS

  • Problem with ERROR27 solved (concerning some old functions data, e.g., A1.32), bug since A3.24

A3.24
B3.23

10.1.2011

INNOVATIONS

  • New possibility of Userinterlock (Menu User): If USER INTERLOCK: MENU is set to “yes”, user and technician now only have access to the Function overview and the menu User. After logging in as expert, it is possible, to changefrom the Function overview to the Main menu by pressing the "SERVICE" key.Setting to “no” everything is the same so far. “No” is the standard setting of the controller.

MODIFICATIONS

  • Simulation Mode acts also on RAS PT
  • Rest of mixer run time is always 20 minutes now. It will be restored after change of direction or activation of enable. Up to now rest of mixer run time was the double value of the set mixer run time in menu Outputs. With it the mixer run time (menu Outputs) can be reduced user-defined for achievement shorter activation times and longer interruptions in the pulses, when there are problems of stability in mixer control circuits.

A3.23
B3.23

12.11.2010

MODIFICATIONS

  • Factory settings are changed to PT1000

A3.22
B3.21

12.11.2010

MODIFICATIONS

  • Bug-fix in  „CHANGE FUNCTION“ and „INSERT FUNCTION“.Bug since A 3.21

A3.21
B3.21

19.10.2010

MODIFICATIONS

  • Bug-fix in Analog function: If value of input variable “Result if (Enable = Off)” is the result of the function itself (“sample & hold”), the information at the display was faulty.

A3.20
B3.19

10.08.2010

INNOVATIONS

  • Support of RAS PT (Room sensor based on PT1000)

A3.19
B3.19

06.07.2010

INNOVATIONS

  • Message dominant ON sets the analog output to 10 volt.

Message dominant OFF sets the analog output to 0 volt.

 

MODIFICATIONS

  • Bug-fix display of Heating circuit controller: In position  “If Heating Circuit OFF, MIXER:” instead of “control” “unchanged” was displayed.Bug since A3.17
  • Bug-fix: If the number of messages was higher than the number of functions, only as many messages have been calculated as defined functions
  • Bug-fix: When the pulse rate of the flow was higher than 10 litres/pulse, the flow rate was not switched over to litres/minute. Bug since A3.17
  • Bug-fix in energy counter of function Heat quantity counter: Inaccuracy occurred in some constellations of quotient and factor. Bug since A3.18

A3.18
B3.18

02.02.2010

INNOVATIONS

  • Possibility of electrical energy counter in function Heat quantity counter:

1. The sources of the input variables flow temperature and return temperature are set to User / unused.

2. Input 15 or 16 has to be set to Impuls/Flow rate, the setting of Quotient means Wh/impulse and not litres/impulse. If the setting range is insufficient, then it can be increased in the Function menu by a factor. For each impulse, the Heat quantity counter is increased by Quotient * Factor (Wh).

  • Display of minutes in function Operation hours counter.
  • Introduction of timestamp at the CAN bus:The controller UVR1611 with node number 1 outputs the timestamp; all other CAN bus devices take over date and time automatically. The timestamp is output every minute.

 

MODIFICATIONS

  • Bug-fixof display of pressure sensors for DL bus. Pressure was displayed too high by factor 10.
  • Bug-fix: If the mixer is set to manual mode and the function Maintenance is active, the function was never ended.
  • Bug-fix in function Heatingcircuit controller:Changing the operation mode to Holiday, Leave or Party Error 27 occurred. Bug since A3.00
  • Bug-fix in function Boiler cascade: If enable = OFF, nominal flow temperature was set to 5°C.
  • Modification of the boiler exchange criterion in function Boiler cascade:So far boilers have been exchanged, if all boilers participating in exchange are ON or OFF after set time. Now, without observance the boiler status, the boilers will be exchanged, when the double set time is increased. Check occurs every 10 minutes.
  • Bug-fix in initialization of Boiler cascade (applying the function at the controller)
  • Calibration in function Heat quantity counter simplified.
  • Correction of wrong translation to English: “flow” instead of “pre-run”, “flow rate” instead of “flow”.

A3.17
B3.04

02.07.2009

MODIFICATIONS

  • Bug-fix of output CAN Data logging values: Speed stages output was not correct.
  • Bug-fix of output values of Heat quantity counter

A3.16
B3.04

09.06.2009

MODIFICATIONS

  • Bug-fix of setting analog outputs 15 and 16 from CAN Monitor or BL-NET.
  • Bug-fix of output data logging values:So far values from the network were displayed without dimensions;
    data of Heat quantity counter 2 had not been output correctly.
  • Bug-fix inoutput 14: Function of UVR1611E (yes/no) has been interchanged: If „no“, DL bus was active, if „yes“ vice versa.
  • Dimension “bar” is now displayed for pressure sensor via DL bus.
  • Bug-fix of display user-defined names:If the name has decreased a certain length, the next name was not or not correctly displayed.

A3.15
B3.04

24.04.2009

MODIFICATIONS

  • Bug-fix of data display of functions 41 to 44 on CAN monitor or BL-NET.
  • Bug-fix: Malfunction by connecting with output variable ”Nominal value” of Profile function.
  • Bug-fix: So far command “Delete All Definitions” in Data logging has loaded the data logging parameters of factory settings.
  • Bug-fix inHeatingcircuit controller: If the amount of time programs is set to zero with nominal values “yes”, the effective nominal room temperature was set to 1°C.

A3.14
B3.04

27.03.2009

MODIFICATIONS

  • Identification of UVR1611E is set invers, if output 14 is set to switch output (reason: compatibility of earlier versions opposite to version 3.13)

A3.13
B3.04

19.03.2009

INNOVATIONS

  • Access on network nodes and data administration is possible now via CAN monitor too.

 

MODIFICATIONS

  • Bug-fix: So far negative speed stages lead e.g., to speed stage 30 for pumps. Now the pump will not be controlled during negative speed stages. Concerns e.g., Analog function
  • Bug-fix: So far, if external sensors are connected to DL bus, output 7 sometimes switched on shortly. Bug since version A3.00.
  • Bug-fix in Boiler cascade and Function control:Output 16 was controlled digitally, although it is not possible to select. Bug since version A3.00.
  • Possibility to activate DL bus in output 14 together with switching output (additionally set UVR1611E to “yes”). Necessary for UVR1611E.
  • In future no display of boot sector at page “Version”, because number of operating systems declares all.
  • Bug-fix: Initializing of Boiler cascade. Bug since version A3.00.

A3.12
B3.04

26.02.2009

MODIFICATIONS

  • Bug-fix: Speed control in mode Phase control. Bug since version A3.00.

A3.11
B3.04

18.02.2009

MODIFICATIONS

  • Bug fix: Data link output (wrong device identification); concerns only version A3.10.

A3.10
B3.04

12.02.2009

MODIFICATIONS

  • Bug-fix: Display of output status Boiler cascade and Function control: Output 16 has been displayed as selected output.
  • Bug-fix: Changing time program parameters via CAN monitor or BL-NET sometimes lead to Error 27.
  • In future the result of Analog function in mode Filter will not be initialized with zero but with the actual value of input variable 1.

A3.09
B3.04

17.1.2009

MODIFICATIONS

  • Bug-fix: When modifying functions, sometimes more memory capacity was calculated than needed.
  • Bug-fix: Display error time programs and user-defined names.

A3.08
B3.04

17.12.2008

MODIFICATIONS

  • Bug-fix inCoolingfunction: Function needed internal more variables memory than necessary; but calculation of function was correct. Bug since version A3.00.
  • Bug-fix: Display of time programs on CAN monitor or BL-NET. Bug since version A3.00.
  • Bug-fix: Timeouts, bug since version A3.00

A3.07
B3.04

17.12.2008

MODIFICATIONS

  • Bug-fix:Connection with output variable nominal temperature of Profile function. Function was calculated wrong, if a connection with the output variable was applied.

A3.06
B3.04

16.12.2008

MODIFICATIONS

  • Bug-fix: Time calculation in following functions:

Analog function: Mode Filter

Heating circuit controller: Average time of outside temperature

Boiler cascade: Delay times

Profile function: Internal cycle

Time switch: Minimum time blocking condition, blocking time

Timer: Pulse time

Data logging via CAN bus: Timeout

A3.05
B3.04

15.12.2008

MODIFICATIONS

  • Bug-fix: Wrong temperature calculation for room sensor RAS in switching position Normal and Lowering.

A3.04
B3.04

25.11.2008

MODIFICATIONS

  • In future the result of Analog function in mode Filter will not be initialized with zero, but with the actual value of the input variable 1.
  • Bug-fix: Pulse time in function Timer was calculated wrong.

Version T3.03 BETA

19.11.2008

MODIFICATIONS

  • Bug-fix: Error in display of timeouts in Function overview

Version T3.02 BETA

19.11.2008

MODIFICATIONS

  • Bug-fix: Error in display Function overview concerning user-defined names of functions.

Version T3.01 BETA

19.11.2008

MODIFICATIONS

  • Bug-fix: Error 27, FSR-Addr: 0357, SPI-Addr: 1CF0

Version T3.00 BETA

11.11.2008

INNOVATIONS

  • Possibility of user-defined names for functions too.
  • Support of DL bus (since serial number 13286). Selection in network inputs, if values are imported from CAN bus or DL bus.
  • Possibility of data logging via CAN bus.
  • Possibility of controlling pumps via 0-10V output (A15, A16) also as PWM (since serial number 41674)

 

MODIFICATIONS

  • Removal of Potentiostat
  • Support of second analog output (A16) (since serial number 41674)
  • Maximal number of functions increased from 40 to 44
  • Bug-fix: Concerning inputs 1 to7 and 9 to 16: Measurement of tension, process value dimensionlessvalueswere displayed too high by factor 10.
  • Bug-fix: Volume flow, analyzedby tension signal, could become negative (reason: tolerances).
  • Bug-fix: Nominal value of Time switch had not the value „Nominal value if time program not fulfilled“ even if the blocking condition was fulfilled.
  • Increasing of the setting range of nominal value of Absolute value control, Threshold value and nominal value of Event control of function PID control from maximal 150°C to maximal 200°C.

Information: All here described modifications and bugs reporting relate only to versions of series 3.xx

Version A2.28

26.9.2008

MODIFICATIONS

  • Bug-fix: Error in User interface editor (Function overview)

Version A2.27

19.8.2008

MODIFICATIONS

  • Bug-fix: Error in function Solar priority. Bug since version A2.26.

Version A2.26

30.5.2008

INNOVATIONS

  • Support of dimension „bar“ (pressure) in measuring tension and in function Comparison.

 

MODIFICATIONS

  • Bug-fix in Solar function in connection with Start function: If there were e.g., 2 Solar functions in a 2-collector system with same priority, only in the active function have been made start tests and no tests in the second function.
  • Bug-fix in Timer function / Instable, concerning the Duty cycle: When Duty cycle was decreasing, the Timer started always again.
  • Bug-fix: If 40 functions were programmed and a function should be deleted, the last function (F:40) was not deleted in the function list.
  • Improvement of signal behavior for controlling newer pumps.
  • Bug-fix Spanish operating system: Texts for ON and OFF were interchanged.
  • Bug-fix: In case of flow measuring over tension input display of negative flow rates was possible.

Version A2.25

5.5.2008

Testversion

Version A2.24

11.3.2008

MODIFICATIONS

  • Bug-fix: User-defined Welcome page was not loaded.Bug since version A2.22

Version A2.23

16.1.2008

MODIFICATIONS

  • Bug-fix in display of dimensions of network inputs.Bug since version A2.21.
  • Bug-fix: Output variable frost protection in function Heating circuit controller was always ON.Bug since version A2.15.

Version A2.22 BETA

16.1.2008

INNOVATIONS

  • Measuring of tensions (0V to 5V) is possible at all inputs. With it the interpretation of volume flow sensors, which output tensions instead of impulses, is possible. Interpretation of flow rates for heat quantity counters is only possible at inputs 1 to 14.

Even if the scaling is adjustable up to 10V, it must be sure, that maximal 5V are active at these inputs.

Version A2.21

29.10.2007

MODIFICATIONS

  • Modification of the setting range of pulse rate (l/pls) in pulse inputs (S15 or S16) and Measuring variable Flow rate to 0.5 – 100 l/pls. If set to >10l/pls the flow rate is displayed in l/min instead of l/h. Therewith it is possible to create a heat quantity counter up to a power of 3000 kW = 3MW.
  • Bug-fix in handling counter in network (interval time and timeouts)

Version A2.20

26.06.2007

INNOVATIONS

  • Possibility of logging two heat quantity counters (HQC) via DL bus:

Logging of network inputs must be set to “yes” (setting in output 14).

Data output UVR1611: The values of the first two HQC’s are output in the function list (as up to now); data output virtual UVR1611: The values of the third and fourth HQC are output in the function list. Thus it is possible to log a total of 4 HQC’s.

Typical application:

2 VSG’s (volume flow encoder) on inputs 15 and 16 of UVR1611;

2 VSG’s on inputs 3 and 4 of CAN I/O module;

4 functions Heat quantity counter at UVR1611.

MODIFICATIONS

  • Network will be initialized 5 seconds after reset (up to now after 20 seconds).
  • Calculation of functions starts 30 seconds after reset (up to now after 20 seconds).

Thus informations from inputs (not from output variables, which are calculated by functions) of other bus members (e.g., room temperature from CAN Monitor, outdoor temperature from another UVR1611) are available at the start of function calculation; thus a short switch on of burner requirement or heating circuit pump is avoided.
(needs CAN Monitors from version E2.00)

  • Bug-fix: Can data logging
  • Bug-fix in Solar priority: If there were more than 8 functions specified, no Solar function was enabled from the ninth.

Version A2.19

26.3.2007

MODIFICATIONS

  • Bug-fix in outputs of network outputs.

Version A2.18

22.3.2007

MODIFICATIONS

  • Bug-fix in display of time programs (problems in displaying of longer function names)
  • Bug-fix in foreign-language versions: During function data transfer from controller to Bootloader no timestamp has been transferred.
  • Wind force will be output to DL bus as solar radiation: 1 km/h corresponds to 1W/m²
  • Bug-fix in output of values of input variables of Analog function via CAN bus combined with digital input variables and offset.
  • Bug-fix in display of output of timeout messages via CAN bus: The text “ANALOG” was not displayed for timeouts of analog network inputs.
  • Modification of function (MAX, MIN, SUM,...) in Analog function only possible as “Expert”.
  • Modification of function (OR, AND,...) in Logic function only possible as “Expert”.
  • Bug-fix in calibration mode of function Heat quantity counter (HQC): The time, which should run from 60 to 0 seconds, was not 60 seconds but 4 minutes. This error had no effect to the calculation of HQC but only to time base of calibration mode. Bug since version A2.15.
  • Bug-fix in output 14 (DL): Output 14 has been partly for 20 seconds „ON“ instead „OFF“ after controller start.

Beta-Version A2.17

17.11.2006

INNOVATIONS

  • In simulation mode the average determination of Analog function will also be deactivated.

 

MODIFICATIONS

  • Bug-fix in controlling of Triac outputs (A1, A2, A6, A7): It could happen, that the Triac was not controlled for a complete half wave (10ms) or that the halve wave was cut as in phase control. Bug since version A2.16.
  • Bug-fix in display of Function overview: Instead of error message “Timeout”, dimension and number of input variable was displayed. Bug since version A2.16.
  • After change of controller node number the CAN bus will be initialized. Thereby the problem, that the access to network nodes, with which the user was connected during change of node number, was no longer possible, is solved. (Bug concerns only controllers in a CAN network).
  • Bug-fix in switching over to Function overview in combination of manual controlling of mixer outputs: When the mixer is manuallycontrolled for longer time, the controller has switched over to Function overview anyway.
  • Increasing the time after which the controller restarts automatically from 1 minute up to 2 minutes (after selection of function data transfer or operating system update by Bootloader)

Beta-Version A2.16ß

28.09.2006

INNOVATIONS

  • Possibility to log network inputs via DL (activation in output 14 of UVR1611).

Requires following operating systems in network:
UVR1611: A2.16
CAN Monitor: E1.14
I/O Module: A1.03
BL-NET: V1.12
and following version of data logger:

BL-NET: V1.12
BL-USB: V2.4
DLOGG: V2.4

  • Output of network output dimensions (PDO’s)

(necessary for data logging of network inputs at UVR1611 via DL)

  • Display of network inputs in Measured values overview with related dimensions


MODIFICATIONS

  • Increasing setting range of  nominal room temperature in function Heating circuit controller
  • Increasing run time (rinsing time) in Start function

Vers. A2.15

27.07.2006

Procedure of update to version A2.15:

1.    Install Memory Manager V2.04

2.    Update Bootloader to V2.3

3.    Install controller operating system A2.15

4.    If in use: Update of CAN Monitor to E1.13

 

INNOVATIONS

  • Simulation mode in User menu available (only as „Expert“):

- no average determination of outdoor temperature in Heating circuit controller

- Inputs defined as PT1000 sensors are measured as KTY sensors

- no RAS interpretation

- The simulation mode will be finished automatically when changing to operating mode “Client” or “Technician” or after power blackout!

  • Display of remaining minimum burner runtime in function status of function Heating requirement.
  • Addition of new Switch-off conditions in Heating circuit controller:

Switch off the heating circuit pump, when the actual flow temperatureT.FlowACT is larger than T.FlowMAX + fixed hysteresis 3K. Pump will be released when T.FlowACT<T.FlowMAX.

  • Possibility to transfer the status of the room sensor RAS via CAN bus (Status room sensor will be transferred automatically with the room temperature. Typical application: Heating circuit built up via CAN I/O Module, room sensor RAS can be connected now directly to CAN I/O module; it is not further necessary as up to now to connect the RAS directly to UVR1611. Needs CAN I/O Module version A1.02.)
  • Possibility in Warm water requirement to start tank feeding onceby key press to set nominal temperature outside of programmed time programs.
  • Input variable “External switch” now accepts also analog values for switching over the operating mode externally:

Value / Operating mode

64 / Stand-by/Frost protection

65 / Time/Automatic

66 / Normal

67 / Lowering

127 / Switch back to internal operation

For possible application via SMS with a later version of BL-NET.

 

MODIFICATIONS

  • Setting range of P and I part of function PID control increased to maximal 100.
  • Increase of setting range value “if enable = OFF” and value of input variables as User in Analog function in mode dimensionless.
  • Increase of setting range for minimum burner runtime in function Heating requirement.
  • Increase of setting range of limit temperature in Solar function to 150°C (necessary for integration solar electrical converters)
  • Bug-fix in switch-on excess in combination with switch-off condition T.FlowNOM<T.FlowMIN:

When the heating circuit was switched-off because of the condition T.FlowNOM<T.FlowMIN, T.flow.NOM was calculated higher and higher by switch-on excess, which became after a certain time higher than T.FlowMIN. Thus the heating circuit pump switched on shortly and after it for a longer time off. E.g., the pump run for 3 minutes every 3 hours. Of course this time could vary depending on set values of switch-on excess and heat curve (T.FlowMIN). As for now the switch-off condition T.FlowNOM<T.FlowMIN will not be considered in connection to switch-on excess.


INCOMPATIBILITIES

  • Setting of new switch-off conditions in Heating circuit controller: Switch off heating circuit pump if T.flowACT>T.FlowMAX (yes/now)

Vers. A2.14

06.06.2006

MODIFICATIONS

  • Problem changing of functions solved: When changing functions all entries of this function were deleted in Function overview; but it is not necessary, if the function type remained and e.g., only the number of time windows has been changed.
  • Installing a user-defined Welcome page is possible again by Memory Manager updating the operating system (inability since version A2.12)

Vers. A2.13

30.05.2006

Procedure of update to version A2.13:

1.  Install Memory Manager V2.03

2.  Update Bootloader to V2.2

3.  Install controller operating system A2.13

4.  If in use: Update of CAN Monitor to E1.12

 

MODIFICATIONS

  • Bug-fix: Changing or inserting Profile function. Bug since version A2.10.
  • Bug-fix: Messages in combination with CAN Monitor. Parts of user-defined names have been changed, but only, when a CAN Monitor is connected to the network and had access to the controller. Bug since version A2.00.
  • Bug-fix Time switch: If nominal value was set to „no“, nominal values have been displayed anyhow. Bug since version A2.10.
  • Bug-fix initialization of operating time counter of function Boiler cascade. Bug since version A2.10.
  • Bug-fix adding, inserting or changing of functions: Controller restarted, when in position „TYPE“ the scroll-wheel was turned into the „wrong“ direction. Bug since version A2.12.

Vers. A2.12

10.05.2006

Procedure of update to version A2.12:

1.  Install Memory Manager V2.03

2.  Update Bootloader to V2.2

3.  Install controller operating system A2.12

4.  If in use: Update of CAN Monitor to E1.12

 

INNOVATIONS

  • Access from controlleralso possible to overview of CAN Monitor (required CAN Monitor version from E1.12)
  • New measuring variable wind speed for supporting wind sensor at pulse inputs (Input 15, 16). Frequency per 1 km/h has to be set as „Quotient“ (setting range from 0,01 Hz up to 1 Hz)
  • New function variable (wind speed and humidity) to set in function Comparison
  • Bug-fix in initialization of Profile function and Heat quantity counter. Bug since version A2.11.
  • Bug-fix in calculation of sensor correction of PT1000 sensors. In case of negative temperature the sensor correction did not operate. Bug since version A1.38)
  • Bug-fix in display CAN Monitor of user-defined names of input variables of functions (e.g., Analog function)

Vers. A2.11ß

30.01.2006

Procedure of update to version A2.11ß:

1.  Install Memory Manager V2.02

2.  Update Bootloader to V2.2

3.  Install controller operating system A2.11ß

4.  If in use: Update of CAN Monitor to E1.11

 

INNOVATIONS

  • Client added, so access to I/O Module is possible.

MODIFICATIONS

  • Bug-fix switch-on delay (did not operate, if an output switched on immediately after reset.

Vers. A2.08

10.01.2006

Procedure of update to version A2.08:

1.  Install Memory Manager V2.02

2.  Update Bootloader to V2.2

3.  Install controller operating system A2.08

 

INNOVATIONS

  • It is possible to analyze also digital input variables in Analog function: If the status is OFF, value 0 will be used for calculation, with status ON the set offset value will be used for calculation. Hence it is e.g., possible to receive an output value proportional to the amount of switched-on outputs

NOTE! Updating elder versions it is necessary to update the boot sector too.

MODIFICATIONS

  • Bug-fix: Display of time programs in Function overview at CAN Monitor

Vers. A2.07

10.11.2005

Procedure of update to version A2.07:

1.  Install Memory Manager V2.02

2.  Update Bootloader to V2.2

3.  Install controller operating system A2.07

 

INNOVATIONS

  • Welcome page can be loaded with function data.

NOTE! Updating elder versions it is necessary to update the boot sector too.

 

MODIFICATIONS

  • Bug-fix display in function Circulation: In mode Time/Pulse T.CR.NOM was not displayed if a time program with nominal value was determined (Displaying: „laut“). But this temperature is active in mode Pulse.

Vers. A2.06

29.07.2005

Procedure of update to version A2.06:

1.  Install Memory Manager V2.02

2.  Update Bootloader to V2.2

3.  Install controller operating system A2.06

 

INNOVATIONS

  • Updating to A2.06 the boot sector is checked automatically and will be actualized if necessary.

NOTE! Updating elder versions it is necessary to update the boot sector too.

 

MODIFICATIONS

  • Bug-fix update operating system: When after update of boot sector the controller was taken off the net, sometimes it was impossible to update an operating system.
  • Bug-fix display of output status at CAN Monitor (problem, if more than 20 functions were programmed.)

Vers. A2.05

09.06.2005

Procedure of update to version A2.05:

1.  Install Memory Manager V2.02

2.  Update Bootloader to V2.2

3.  Install controller operating system A2.05

 

INNOVATIONS

  • Updating to A2.05 the boot sector is checked automatically and will be actualized if necessary.

NOTE! Updating elder versions it is necessary to update the boot sector too.

 

MODIFICATIONS
- Bug-fix data transfer

Vers. A2.04

03.06.2005

Procedure of update to version A2.04:

1.  Install Memory Manager V2.02

2.  Update Bootloader to V2.2

3.  Install controller operating system A2.04

 

INNOVATIONS

  • Updating to A2.04 the boot sector is checked automatically and will be actualized if necessary.

NOTE! Updating elder versions it is necessary to update the boot sector too.

 

MODIFICATIONS

  • Bug-fix input 15: If input 15 was set to measuring variable „Pulse“, no impulse was sent to the function.
  • Bug-fix display of calibration differences at CAN Monitor (was not displayed so far)

Vers. A2.03ß
B2.03

12.04.2005

Procedure of update to version A2.03:

1.    System requirements: Memory Manager V2.01 and Bootloader V2.00

2.    Update boot sector UVR1611 version B2.03: download and actualize

3.    Install operating system A2.03

INNOVATIONS

  • Display of rest of mixer run-time in function Mixer control (output variables) and Heating circuit control (Function status)
  • Mixer run-time will be reloaded (concerning Heat circuit control and Mixer control), when mixer is in manual mode, in protection mode (message dominant ON or OFF) or in automatic mode operating „OPEN“ or „CLOSE“.

MODIFICATIONS

  • Bug-fix: control of Triac outputs (when output should be on full speed, sometimes short irregular blackouts happened.
  • Bug-fix in average calculation (concerning average calculation of outdoor temperature Heating circuit control and Filter mode in Analog function, if average is set to 1,0h or 1,5h)
  • Bug-fix in calculation of Flow rate in input 16 (calculation result was always 0 l/h, if measuring value Pulse was selected.

Vers. A2.02ß
B2.02

31.03.2005

MODIFICATIONS

  • Bug-fix in display of user-defines names and nominal value in time programs on CAN Monitor.
  • Bug-fix in network timeouts (only concerning network inputs, which were not defined).

 

Procedure of update to version A2.02:

1.    System requirements: Memory Manager V2.00

2.     Download and update Bootloader firmware BL232 V2.00

3.    Update boot sector UVR1611 version B2.02: down-load and actualize

4.    Install operating system A2.02

Vers. A2.01ß
B2.01

02.03.2005

MODIFICATIONS

  • Bug-fix in calculation of rate of rise (at low temperatures and large rate of rise).
  • Bug-fix in page output via CAN bus in combination to CAN Monitor in function Timer.
  • Bug-fix in output of output statuses (only occurred, if output 14 was set to switch output)
  • Bug-fix in connection to device testing program (error in boot sector).

Vers. A2.00ß
B2.00

02.03.2005

INNOVATIONS

  • Implementation SDO protocol (necessary for communication with CAN Monitor)

Vers. A1.57ß
B1.06

08.02.2005

INNOVATIONS

  • For designation of timer functions more designations are available


MODIFICATIONS

  • Bug-fix in display during data transfer with BL 232 (function data string was displayed wrong)
  • Bug-fix in function Solar priority: An involved solar function set to OFF was released anyway.
  • Bug-fix in function Counter: Counter of previous day was not only actualized by change of date => thus wrong display of value appeared. The total actual count was not affected by this bug.
  • MANUAL ON mode starts 20 seconds after reset.
  • Bug-fix in display of function Heat quantity counter.  The value of performance fluctuated in some operating modes around 2.56 kW.
  • Bug-fix in Profile function: Error 27 occurred applying a Profile function at the controller itself, if more than 31 stages are defined.
  • Maximum value of setting values in PID controller increased to 150 instead of 99.
  • Bug-fix in network: If network release was set OFF, timeout errors have been displayed anyway.

Vers. A1.56
B1.05

10.01.2005

MODIFICATIONS

  • Bug-fix in function Comparison (comparing pulses)
  • Bug-fix in Heating circuit control (Maintenance mode was never ended if mixer behaviour was set to unchanged or control.

Vers. A1.55ß
B1.05

10.08.2004

MODIFICATIONS

  • Bug-fix of flashing of page Version

Vers. A1.54ß
B1.05

24.05.2004

INNOVATIONS

  • In Analog function it is possible to set an offset value to each input variable additionally.
  • Additional input variable in function Warm water requirement: External switch. If this input variable is set to ON, only T.WW.MIN will be required.
  • Additional measuring value in inputs 15 and 16 under TYPE: PULSE, adjustable: Pulse. Thus adding up of pulses via pulse counter is possible
  • Integration of a further service function „Output status“ in menu Outputs supporting troubleshooting.

MODIFICATIONS

  • In function Counter an additional divider can be set.
  • In function Synchronisation it is adjustable, if a time window occurs once or cyclically (in setting „once“ it is possible to realize a holiday function for several functions (link to Heating circuit control and Warm water requirement via external switch and to PID control for preparation of hot water without volume flow switch  and function Circulation via enable).
  • Bug-fix in Warm water requirement: Error only occurred, when nominal warm water temperature was not set to user but linked to an output variable of another function.

 

INCOMPATIBLITIES

  • Offset in Analog function

Vers. A1.53ß
B1.03

26.04.2004

MODIFICATIONS

  • Bug-fix in addressing of network variables in combination with input variables in input areas (Analog function, digital function and operating hours meter.

Vers. A1.52ß
B1.03

15.04.2004

INNOVATIONS

  • Addition of Timeouts in network inputs

 

MODIFICATIONS

  • Bug-fix in addressing of network variables in combination with digital input variables

Vers. A1.51ß
B1.03

02.04.2004

NEW: Betaversion for network

  • Bug-fix in function Comparison

Vers. A1.50ß
B1.03

02.02.2004

NEW: Beta version for network

  • Implementation Can bus (Communication at present only via PDO)

Vers. A1.44
B1.07

29.08.2005

MODIFICATIONS

  • Bug-fix in calculation of rate of rise (at low outdoor temperatures and large rate of rise)
  • Bug-fix of controlling the Triac outputs (When output should be at full speed, sometimes irregular short blackouts occurred anyway.).
  • Bug-fix in average calculation  (concerning average calculation of outdoor temperature Heating circuit control and Filter mode in Analog function if average time was set to 1.0h or 1.5h.).

Vers. A1.43
B1.06


NEW:

  • For designation of timer functions more designations are available

 

MODIFICATIONS

  • Bug-fix in display during data transfer with BL 232 (function data string was displayed wrong)
  • Maximum value of setting values in PID controller increased to 150 instead of 99.

Vers. A1.42
B1.05

20.12.2004

MODIFICATIONS

  • Modification of measuring temperatures of sensor 8 (in first 20 seconds sensor 8 was activated in mode Current measuring).  Bug since version A1.41.
  • Bug-fix in function Counter: Counter of previous day was not only actualized by change of date => thus wrong display of value appeared. The total actual count was not affected by this bug. Bug since version 1.38.
  • Modification Heating circuit control: If mixer behaviour in switch-off conditions was set to unchanged, the mode Maintenance was never finished (only by power blackout)
  • Bug-fix Solar priority function: involved solar functions set to OFF were released anyway.

Vers. A1.41
B1.05

04.11.2004

MODIFICATIONS

  • Bug-fix function Heat quantity counter: The value of performance fluctuated in some operating modes around 2.56 kW.
  • Bug-fix in Profile function: Error 27 occurred applying a Profile function at the controller itself, if more than 31 stages are defined.
  • Bug-fix in function Comparison: Comparison did not operate comparing operating hours.
  • MANUAL ON mode starts 20 seconds after reset.
  • Prevention of short switch-on of some outputs after reset

Vers. A1.40
B1.05

24.05.2004

MODIFICATIONS

  • Bug-fix in function Warm water requirement: Error only occurred, when nominal warm water temperature was not set to user but linked to an output variable of another function.

Vers. A1.39
B1.05

04.05.2004

INNOVATIONS

  • In Analog function it is possible to set an offset value to each input variable additionally.
  • Additional input variable in function Warm water requirement: External switch. If this input variable is set to ON, only T.WW.MIN will be required.
  • Additional measuring value in inputs 15 and 16 under TYPE: PULSE, adjustable: Pulse. Thus adding up of pulses via pulse counter is possible
  • Integration of a further service function „Output status“ in menu Outputs supporting troubleshooting.

MODIFICATIONS

  • In function Counter an additional divider can be set.
  • In function Synchronisation it is adjustable, if a time window occurs once or cyclically (in setting „once“ it is possible to realize a holiday function for several functions (link to Heating circuit control and Warm water requirement via external switch and to PID control for preparation of hot water without volume flow switch  and function Circulation via enable).

 

INCOMPATIBLITIES

Offset in Analog function

Vers. A1.38
B1.03

07.04.2004

INNOVATIONS

  • Display of name of function data and status in Data administration.
  • Sensor check (short circuit, interruption) in analog inputs possible.
  • Adjustable value for sensor correction in analog inputs.
  • Frost protection mode in Heating circuit control also in dependence on room temperature.

 

MODIFICATIONS

  • If a room sensor is indicated in function Heating circuit control and the sensor is short-circuited, the Heat circuit control operates in parameterization as there would be no room sensor indicated

Vers. A1.37
B1.03

23.02.2004

MODIFICATIONS

  • Bug-fix in function overview of Function control.
  • Bug-fix of error in scaling of input 8 and measuring variables tension, current and resistance. Bug since version A1.34.
  • Bug-fix in combination with Solar, Solar priority and Start function

Vers. A1.36
B1.03

02.02.2004

INNOVATIONS

  • Possibility to insert also the output variables into Function overview.
  • Possibility of adjustment the storage of errors in Function control
  • Possibility to release a reset impulse in Messages by pressing the scroll wheel.
  • In mode Time/Auto resp. RAS (Time/Auto) additionally it will be displayed, if the heating circuit is in normal or lowering mode because of the time windows.

MODIFICATIONS

  • Bug-fix function Maintenance if no mixer was specified. Bug since version A1.35.
  • Modification of display of user-defined messages.
  • Bug-fix Timer function: If pulse time is set to >18h, the timer run-time was calculated wrong. Bug since version A 1.35:
  • Bug-fix in function Time switch (only in combination with blocking input)
  • Modification of line skip in Function overview
  • Bug-fix in display of Heating circuit control: In operating mode Holiday or Leave with each day the end of holiday or leave was incremented by 1 (Only in display; the function operated right.).
  • Creating a reset pulse is only possible in message type „malfunction“.
  • Bug-fix boot sector: If “Factory Settings Overwrite?“ was selected for data download (BL232 =>UVR1611), the data have not been overwritten completely.

 

INCOMPATIBILITIES

  • Setting, if errors should be stored in Function control.

Vers. A1.35
B1.02

16.11.2003

INNOVATIONS

  • Additional designation for Analog and  Digitalfunction inserted.
  • Addition of output variables in Heating circuit control: status of maintenance and frost protection mode.
  • New operating mode in Heating circuit control: MALFUNCTION, if outdoor temperature is measured >100°C, 0°C are supposed.
  • Additional parameter in Heating circuit control: Rate time, depending on outdoor temperature.
  • Output variable added in Solar function: maximum threshold reached (T.Ref.MAX or Z.Lim.MAX)
  • Output variable added in function Synchronisation:Status Controller Start
  • Input variable added in Profile function: Nominal value, if enable = OFF.
  • Input variable added in Timer function: Duty cycle
  • New mode in Analog function: Filter
  • Addition of Eco operation in function Heating requirement; addition of an own enable for each boiler stage in function Boiler cascade.
  • Circulation Function is able to analyze a digital status (e.g., flow switch) as warm water temperature.
  • Code for Expert adjustable (0000 – 9999).

MODIFICATIONS

  • Bug-fix in activated switch-off by room temperature and heat curve rate of rise.
  • Enables in Heating circuit control are ignored when heating circuit is in operating mode maintenance.
  • Bug-fix in Analog function if enable = OFF
  • Extension of Profile function to 64 stages.
  • Modification of resolution of Profile function values in mode temperature to 0,5°C.
  • Modification of designations in Heating circuit control:

T.RoomMIN =>T.RoomLOWER

T.RoomNOM =>T.Room.NORMAL

Additional Display of the effective nominal room temperature: T.RoomEFF.

  • Optimize of Mixer control: Mixer reacts faster


INCOMPATIBILITIES

  • Average calculation in Heating circuit control
  • Values of Profile function in mode temperature
  • Reason of Message

Vers. A1.34
B1.02

01.10.2003

INNOVATIONS

  • Function Synchronisation added.
  • Profile function added.
  • Function Boiler cascade added.
  • Warmwater requirement provides output variable warm water nominal value.
  • Deleting a message causes a pulse (3 seconds) at a selectable output.
  • For release a message the status of the input variable „Activate message“ must  endure ON for 10 seconds.
  • Addition of a Flip-Flop function in Logic function
  • Possibility to compare volume flows in function Comparison.
  • Volume flow in function Heat quantity counter is adjustable by user too.
  • Two further modes in Analog function: Mean Value and Sum
  • Further mode in function Circulation: Time/Pulse: if time window is not active, controller operates in mode „pulse“.

 

MODIFICATIONS

  • Bug-fix in Solar priority
  • If an output (A1, A2, A6 or A7) is defined as speed control output and the speed stage 0 was committed from a function, the output status was AUTO/ON; now it is AUTO/OFF  and the display symbol is also OFF;
  • Bug-fix in Logic function: If input variable no.6 had value 1, the inverse output was always ON
  • Base temperature in Heating requirement operates only if nominal temperature is>5°C.

 

INCOMPATIBILITIES
- Check modeCirculation


!!!!NOTE!!!!ATTENTION!!!!NOTE!!!!

  • With Bootloader version B1.01 it is not possible to save function data on the Bootloader. Therefore it is recommended not to update (A1.32 to 1.34).

Vers. A1.33
B1.01


INNOVATIONS

  • The rate of rise is adjustable in Heating circuit control.
  • Increase of maximal number of function from 32 to 40.
  • Message added
  • Anti-Skid control added

 

MODIFICATIONS

  • Mode pulse in function Circulation extended and improved.

INCKOMPATIBILITIES

  • Check the tank temperature and parameterizing of mixture protection in function Circulation.
  • Check Anti-Skid control.

Vers. A1.32
B1.01

27.06.2003

INNOVATIONS

  • Menu Data Administration added
  • Support of 7 memory positions in Bootloader
  • Modification and saving of factory setting as new factory setting
  • Welcome page individual programmable only in combination with Memory Manager

MODIFICATIONS

  • Bug-fix of Circulation function: Nominal value was output in time program even when nominal value was set to no applying the function. Bug since version A1.30
  • Bug- fix of User Interface Editor: Sometimes it was impossible to insert lines.
  • Bug-fix in download of factory setting: Parameters of analog output have not been initialized. Bug since version A1.30.
  • Bug-fix of volume flow encoder: In future, when the volume flow encoder does not output pulses, it will not be waited more than 5 minutes until volume flow is set to 0, but the volume flow decreases to 0 according to the time since the last pulse.


INCOMPATIBILITIES

  • In elder versions of boot sector of controller (until B1.00) always the first memory position of the Bootloader will be activated (first of 7 positions of Bootloader)

    !!!!NOTE!!!!ATTENTION!!!!NOTE!!!!

Updating the operating system version A1.32 all function data will be transferred to a changed format and stored. Function data of version A1.32 are not downward compatible and therefore cannot be processed by older versions (version < A1.32). It is also NOT allowed to change the operating system to an older version.

Vers. A1.31ß

21.05.2003

INNOVATIONS

  • Extension of Timer function
  • Function control added


MODIFICATIONS

  • Bug-fix in Heating circuit control and Mixer control (problem in counter handling)
  • Bug-fix in function Time switch (it was not possible to set days and times)
  • Bug-fix in Analog function (problem with number of input variables if function was not enabled) and Digital function (problem with number of input variables if function = ZERO)

Vers. A1.30ß

06.05.2003

INNOVATIONS

  • Freely configurable Function overview

    MODIFICATIONS
  • Bug-fix time management
  • Pulse of VSG (Volume flow encoder) will be provided to all functions.

Vers. A1.27

15.05.2003

MODIFICATIONS

  • Bug-fix in Analog and Digital function (If Analog function was not enabled, the time windows were not displayed right, as well if the Digital function was set to OFF)
  • Bug-fix in inserting/changing of functions

Vers. A1.26

24.04.2003

INNOVATIONS

  • Solar Start function enables assignment of involved functions.

    MODIFICATIONS
  • Bug-fix in Maintenance, Start function and Priority function: If in mentioned functions no involved Solar function or Heating circuit control was selected, the controller wrote permanently into EEPROM until it was damaged.

Vers. A1.25

18.03.2003

MODIFICATIONS

  • Bug-fix of function Time switch: Enable mode was not only limited to normal/inverse.
  • Bug-fix in function Heat quantity counter: Partly the data of 15th or 16th function have been destroyed.
  • Bug-fix in functions Heat quantity counter and Counter: When the external counter reset was permanent active, the controller wrote permanently into EEPROM
  • Actual counts (functions Heat quantity counter, Counter and Potentiostat) will only be stored once a day generally.
  • Bug-fix in deleting or modifying of functions: Error only occurred if the maximal number of functions (32) was defined.

Vers. A1.24

17.02.2003

INNOVATIONS

  • The version of Bootloader (of controller) will also be displayed on page Version. In previous Bootloader versions following term will be displayed because of programming reasons: “BW “

 

MODIFICATIONS

  • 120 minutes after last key pressing user mode will be set to User automatically.
  • Bug-fix in Cooling function: Selection of second output variable of Cooling function could not be used as input variable in another function.
  • Bug-fix in function Heat quantity counter: Calculation of values (kW, kWh) was wrong at frost protection share >0%

Vers. A1.23

22.01.2003

INNOVATIONS

  • Cooling function added
  • Function Mixer control added
  • Mode of input status is possible to change to inverse for all digital input variables (up to now only in case of enable possible).
  • Output 15 (analog) is also selectable in output variables of all functions
  • Output 15 (analog) is made configurable
  • Manual setting of speed stages for speed controlled outputs (A1, A2, A6, and A7) in mode HAND/ON possible.
  • Linking of functions retain also in case of deleting functions.
  • Possibility to insert functions in function list
  • Function Maintenance overwrites on analog output all other functions (but digital command has first priority nevertheless).
  • Non-linear heat curve (see Incompatibilities)
  • Functions Counter and Heat quantity counter provide output variables for actual counts and have an input variable for counter reset
  • Possibility to compare actual counts of function Counter or Heat quantity counter in function Comparison

    MODIFICATIONS
  • Modification in Heating circuit control: In mode Maintenance output of output variables T.FlowNOM = 5°C and T.Room.EFF = 25°C.
  • Bug-fix in scaling output 8: Wrong values have been calculated sometimes.
  • T.FlowNOM will be set to T.Flow.MAX if outdoor sensor displayes -999°C (=short circuit) in Heating circuit control.
  • Difference in mode „Time“ acts upwards in function Circulation (see Incompatibilities).
  • Bug-fix in time programs: Error occurred, if time programs have been programmed as well as with as without nominal values only in combination with functions Heating circuit control, Warm water requirement and Circulation.

    INCOMPATIBILITIES
  • Selection of outputs is reorganized in functions PID Control, Warm water requirement (only boiler modulation) and maintenance
  • !!! Check assignment of outputs!!!
  • Adjustments of DIFF.ON and DIFF.OFF in mode „Time“ of function Circulation have to be checked (see Modifications)
  • Non-linear heat curve (Flow temperature at +20°C now corresponds to flow temperature at +10°C and must be corrected.)

Vers. A1.22

11.12.2002

INNOVATIONS

  • Function Comparison dimensionless
  • Comparison of radiation sensors is possible too
  • Bug-fix of function Maintenance (Setting parameter was output as burner performance
  • Bug-fix in Enable of Analog function and Digital function (Enable was OFF after update to version A1.21)

Vers. A1.21

23.10.2002

INNOVATIONS

  • Extension of data output with time information
  • Automatic switch over between normal and summer time.
  • Only User cannot change names.
  • Frost-protection mode for Heating circuit control
  • Switch-over possibility with digital input for frost-protection mode.
  • Output variable of effective room temperature.
  • Hysteresis of switch off condition room temperature can be set in 0,1K steps.
  • If Warm water requirement = OFF, output of T.WW.EFF = 5°C
  • Operating hours counter displays also count of previous day.
  • Correction value for RAS01 added
  • Negative differences can be set.
  • DIFF.ON and DIFF.OFF are meaningfully limited.
  • Output can also be used as input variable
  • Inverse enable of functions possible
  • Analog input S8 for tension, current or resistance measurement.
  • Introduction of Designer groups
  • Start of test program via CAN bus
  • Enable of Analog and Digital mode
  • Setting offset values in Analog mode by user


MODIFICATIONS

  • Output of temperatures via Data link
  • Heating requirement
  • Bug-fix of function Maintenance (Setting parameters was output as burner performance)
  • Function Maintenance: Burner performance to analog output
  • Modification Enable of Analog and Digital function (after update to version 1.21 enable was OFF).
  • Modification time routine  (changing day in summer time occurred only at 1:00 am)
  • After-run time of speed control output
  • Bootloader sector improved
  • Nominal values for test program (new testing device)

    INCOMPATIBILITIES
  • Updating from version A1.19 and A1.20 it is necessary to check Enable of Analog and Digital function.

Vers. A1.20

14.09.2002

MODIFICATIONS

  • Addressing of time programs
  • Data output

Vers. A1.19

30.09.2002

INNOVATIONS

  • Operating system download possible
  • Data output via Data link

    MODIFICATIONS
  • Bug-fix time programs in functions (If number of time programs in functions is set to 0 , all settings of other time programs have been deleted.).

 

 