The UVR61-3 unit has various functions for use in solar thermal systems and heating systems: thermostat, differential temperature, and speed control. The desired control function is specified by means of entering the respective program number. Summary of functions: - 6 sensor inputs
- 1 speed-controllable output
- 2 other outputs optional (with additional relay module)
- 1 analogue output, 0 - 10 volts
- Each with 3 functions for differential, minimum and maximum
- Integrated heat meter
- Freely programmable time switch
- Easy-to-read display with various icons
- Time, date
- Data line (to analyse the temperature with a PC via D-LOGG or BL-USB)
- System function control
- Solar start function, collector temperature delimiting, anti-freeze function
- Overvoltage protection at all inputs
Art. no.: 01/UVR61-3 Art. no.: 01/UVR61-3-R (with relay module)
| Differential temperatures: | adjustable from 0 to 99 °C | | Minimum / maximum threshold values: | adjustable from -20 to +150 °C | | Accuracy: | typ. ±2% | | Operating voltage: | 230 V AC 50-60 Hz | | Power consumption: | max. 3 VA | | Rated current load: | max. 1.5 A resistive-inductive cos phi 0.6 | | Fuse: | 3.15 A quick-blow (unit + outputs) | | Transformer: | short-circuit proof | | Protection class: | II - protective insulation | | Protection degree: | IP40 | | Dimensions (W/H/D) | 152 x 101 x 48 mm | | Weight: | 210 g | | Permissible ambient temperature | 0 to 45 °C | | Accessories: | UVR61-3 UVR61-3-R | UVR61-3-R4 | UVR61-3-R5 | UVR61-3-R6 | | | | | | | The following files pertaining to this product can be found in our download area: | | Manuals: |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
|